Message: | HCJ3 12KV 630A vacuum interrupter for vacuum contactor
1. Brief introduction
The interrupter adoption porcelain and ceramics makes to insulate the outer shell. Contact is WCCu metal alloy material advanced technique of adoption Including bulk small. Breaking the abiliting strong the life span is long, maintenanle is simple ,no explosion dangerous, no contaminate and the noise is low . The pack vacuum contactor can operate the ebery kind of electric appliances equipments, and fuse match f-c cabinet
2. Vacuum Tube main technique parameter
Rated voltage: 12 kv
Rated cureent: 630A
Rated making current: 6.3KA
Rated breaking current: 5.04KA
Limiting breaking current: 6.3KA
Rated short-time withstand current: 6.3KA
Rated short-time withstand voltage: 42 kv
Rated lighting impulse voltage: 75 kv
Circuit resistance at lowest rated contacts force: ≤80μΩ
Electrical life: 250,000 times
Mechanical life: 5000,000 times
Closing force due to bellows and atmosphere: 70±20 N
Force required to hold contacts open at full stroke: 100±30 N
Limiting abrasion of contacts: 3 mm
Internal gas pressure: ≤1.33×10-3 Pa
Storage life: 20 years
No. Parameter name Unit Value
1 Rated voltage kV 12
2 Rated current A 630
3 Rated frequency Hz 50
4 Rated making current kA 6.3
5 Rated breaking current kA 5.04
6 Limiting breaking current kA 6.3
7 Rated short-time withstand current kA 6.3
8 Rated short-time withstand voltage kV 42
9 Rated lighting impulse voltage kV 75
10 Circuit resistance at lowest rated contacts force μΩ ≤80
11 Electrical life Times 250000
12 Mechanical life times 500000
13 Closing force due to bellows and atmosphere N 70±20
14 Force required to hold contacts open at full stroke N 100±30
15 Limiting abrasion of contacts mm 3
16 Internal gas pressure Pa ≤1.33×10-3
17 Storage life years 20 |