Message: | Detailed product description:
The vacuum contactor is mainly used in the power system with AC 50Hz and rated voltage 12kV, for making or breaking circuit and to make electromagnetic starter with suitable protective device and F-C switchgear.
Working condition:
1) Altitude should not be over 1,000m;
2) Ambient temperature: -5~40°C;
3) Average temperature in 24 hour not exceed 35°C;
4) When the highest temperature is 40°C, the relative humidity should not be higher than 50%;
5) Pollution degree: class 3
.Main models and technical parameters
Rated voltage: 12 KV
Control voltage: 220/110/380
Rated current: 160A, 250A, 400A, 630A
Clearance: 5±0.5 mm
Over travel: 2±0.2 mm
Pressure: >85N
Main circuit power frequency withstand voltage: 42000 v
Auxiliary circuit power frequency withstand voltage: 2500 v
Control circuit power frequency withstand voltage: 2000 v
Making capacity: 10Ie,100 times
Breaking capacity: 8Ie,25 times
Limit opening current(A): 10Ie
Overload: 8Ie,10 s
Mechanism life: 1 million times
Weight: 30KG
Note: “Ie” represents the rated current of main circuit |